Solid Grounding - Working, Phasor Diagram, Advantages and Disadvantages

 Working: 

In this method, the neutral is earthed using the pipe type or plate type earthing.

One or two earth electrodes are employed depending upon the need.

Fig. Shows the Solid  type earthing

We shall now discuss what happens when a single line to ground fault occurs. Let us suppose that the earth fault occurs on phase B. 

The potential of B becomes zero but there is no change in the potential of the healthy phases R and Y. There are three components of the current of phase B :

1. Current INR - which flows from phase B to fault to capacitance Cto phase R.

2. Current INY - which flows from phase B to fault to capacitor C to phase Y.

3. Fault current IF - which flows from phase B to fault to ground.

The value of the fault current depends on the zero sequence impedance from the phase conductor of the power source up to the fault point. 

Normally the resistive component of the zero-sequence impedance is negligible.

So the fault current IF lags behind the faulty phase voltage VBN by 90°. 

Vector diagram is shown in the figure. 

Current INR and INY flow due to the voltages VNR and VNY respectively. Vector VNR is obtained by reversing the vector VRN. Current vector INR is ahead of voltage vector VNR.

Similarly, vector VNY is obtained by reversing the vector VYN. Current INY is ahead of voltage VNY by 90°. 

The vector sum of currents INR and INY is current  ICF which is 180°  out of phase by fault current IF.

Advantages :

1. Potential of the faulty phase becomes zero but the potential of the healthy phases remains the same.

2. Fault current and the charging current becomes out of phase by 180° i.e. they get neutralized. This prevents or reduces the problem of arcing ground.

3. Discrimination type protection can be given as the heavy fault current flows.

4. There is no ill effect on the insulation of the equipment connected to the line as there is no increase in voltage of the healthy phases.

Disadvantages and limitations :

1. The system may become unstable as the value of the fault current becomes large

2. It becomes difficult to handle the circuit breaker as the heavy current has to be interrupted

3. The disturbances are produced on the nearby communication lines due to the heavy fault current.

Due to the above disadvantages, this type of earthing is used only where the impedance of the circuit is more. This system is employed up to 33 kV.

Previous Post Next Post